Searchpoint Optima Plus IR Gas Detector, Hydrocarbon, UL/INMETRO, non-HART
Part number
2108B2101N

Stainless steel infrared point detector for flammable hydrocarbon gases in hazardous areas. Its dual-compensated optics give fast, fail-to-safe detection with a 4-20 mA output and no exposure to catalytic poisons.
UL / INMETROApproval
1.6 kgWeight
IP66/67Ingress protection
Specifications
| Model | 2108B2101 + N (non-HART) |
|---|---|
| Target gas | hydrocarbons (factory gas setting) |
| Approval | UL / INMETRO |
| Measuring range | 0-100 %LEL hydrocarbons |
| Detection principle | 4-channel dual-compensated infrared |
| Output | 4-20 mA sink or source (non-HART version) |
| Supply | 18-32 VDC (24 VDC nominal), <4.5 W |
| Material | 316 stainless steel |
| Weight | 1.6 kg |
| Response time | T90 <4 s (methane) |
| Operating temperature | -40 to +65 °C |
| Ingress protection | IP66/67 |
Standards
- ULUL File E91044 Class I Groups B, C, D
- INMETROINMETRO TÜV 12.1017 X BR-Ex d IIC T4/T5 IP66/67
- IECIEC 61508 SIL 2
Related items

XNX Universal TransmitterXNX-UTAE-NNNNNXNX Universal Transmitter, UL/CSA, aluminium, EC personality

FSL100 Series Flame DetectorFSL100-UVIRFSL100-UVIR Ultraviolet/Infrared Flame Detector

Searchpoint Optima Plus Infrared Point Gas Detector2108B2001NSearchpoint Optima Plus IR Gas Detector, Hydrocarbon, ATEX/IECEx, non-HART

XNX Universal TransmitterXNX-UTAI-NHNNNXNX Universal Transmitter, UL/CSA, aluminium, IR personality with local HART

XNX Universal TransmitterXNX-AMAV-RHNNNXNX Universal Transmitter, ATEX/IECEx, aluminium, mV personality with relay option, local HART

XNX Universal TransmitterXNX-UTAI-RNNNNXNX Universal Transmitter, UL/CSA, aluminium, IR personality with relay option

XNX Universal TransmitterXNX-AMAI-NNNNNXNX Universal Transmitter, ATEX/IECEx, aluminium, IR personality

XNX Universal TransmitterXNX-AMAV-NHIC1XNX Universal Transmitter, ATEX/IECEx, aluminium, mV personality with local HART, MPD IR CO2 sensor